Señales UL acordes a NFPA 101
Las señales UL se utilizan en todos aquellos proyectos en los que se tenga que aplicar la norma NFPA 101, la cual nos indica que los medios de egreso han de ser señalizados a nivel de suelo o pared por balizamientos acorde a UL 1994.


NFPA 101 2018 EDITION
7.10.1.7* Floor Proximity Egress Path Marking. Where floor proximity egress path marking is required in Chapters 11 through 43, an approved floor proximity egress path marking system that is internally illuminated shall be installed within 18 in. (455 mm) of the floor. Floor proximity egress path marking systems shall be listed in accordance with ANSI/UL 1994, Standard for Luminous Egress Path Marking Systems. The system shall provide a visible delineation of the path of travel along the designated exit access and shall be essentially continuous, except as interrupted by doorways, hallways, corridors, or other such architectural features. The system shall operate continuously or at any time the building fire alarm system is activated. The activation, duration, and continuity of operation of the system shall be in accordance with 7.9.2. The system shall be maintained in accordance with the product manufacturing listing.